June 2016: Trowel Tech

Words: Dan KamysJune 2016

Jeremy DouglasJeremy Douglas

Mason contractors across the country face similar challenges when out in the field. With the help of Hohmann and Barnard’s director of technical services, Jeremy Douglas, Masonry delivers answers to some of your most technical, complicated questions. Q. We’ve been seeing larger brick veneer wall cavity spans over the last several years, but the veneer anchors we have been using are still the same. Can standard veneer anchors handle the loads they need to within these larger cavities? A. Sure, I address this issue pretty much every day of the week in one way or another. This has become a major concern for several reasons. First, while the TMS-402 code only requires a 1-inch air cavity, most designers and masonry entities recognize that a larger air cavity is more desirable. Because construction tolerances of the backup and veneer walls typically run at ±1/4 inch, they potentially jeopardize 50 percent of that airspace should they run outboard and inboard of those tolerances, respectively. Additionally, the need for higher R-values in our exterior continuous insulation has increased the span, as has the expanded use of mineral wool insulation to more easily create NFPA 285-compliant assemblies. We also see larger airspaces today to help to better achieve pressure equalization between the air in the cavity and the outside. The same TMS-402 referenced above states that a 4 1/2-inch maximum distance between the inside face of the veneer and the steel framing, masonry, or concrete backing, with a minimum of 1 inch of air space, shall be specified. This means that, currently, we must provide engineering calculations for any cavity spans larger than 4 1/2 inches. What the code doesn’t suggest is any specific performance criteria for any anchors to be held to in order to be considered adequate. The closest thing the masonry industry has to a performance standard regarding anchor load capacities would be Tech Note 44B as published by the Brick Industry Association. 44B suggests we should be working only with ties that show maximum deflections of less than 0.05 inch (1.2 mm) when tested at an axial load of 100 lbs. in tension or compression. Sounds pretty straightforward, right? Well, not exactly. Two-part masonry anchors often consist of a portion of the anchor fixed to the backup wall and an adjustable tie, usually formed from 3/16-inch wire to be embedded in the veneer joint. If we’re considering a performance standard as I suggested above, that standard must apply to the anchor/tie combination everywhere within its plane of adjustability. As an example, the TMS-402 code allows for 3/16-inch pintle hook anchors to be offset no more than 1 1/4 inches. In evaluating how a standard round wire pintle performs across this 1 1/4 inches of adjustability, testing a standard wall configuration inside the 4 1/2 inches shows us a nearly 90 percent reduction in strength from the point where the pintle and anchor are completely engaged to where the pintle is offset 1 1/4 inches. This hasn’t even taken into account changes in pintle size or larger airspaces, brick corbelling, or other scenarios where the airspace can potentially become larger than 3 inches. So, to answer the question, a standard masonry anchor may or may not be able to handle the expanded cavity. A lot of factors need to be taken into consideration, which is why the code calls for engineering calculations beyond 4 1/2 inches. You may also see anchors referred to as “high strength” or as being specifically manufactured for “wide cavity walls” to address some of the concerns mentioned above. For now, the only way to be certain is for engineering personnel to evaluate testing that shows the load performance of the anchor throughout its adjustability and specific to the conditions in which it will exist.
Jeremy Douglas, CSI, CCPR, has nearly 20 years of experience in the masonry industry working with veneer systems. He is director of architectural services for Hohmann & Barnard and can be reached at JeremyD@h-b.com.
The Evolution and Innovation of Concrete Unit Pavers
May 2025

When concrete unit pavers were first produced in Europe after the second World War, they were used as a replacement for clay brick pavers due to a lack of raw materials needed to produce that product. The primary emphasis was function with little to no co

The Evolution and Innovation of Concrete Unit Pavers
May 2025

When concrete unit pavers were first produced in Europe after the second World War, they were used as a replacement for clay brick pavers due to a lack of raw materials needed to produce that product. The primary emphasis was function with little to no co

Masonry Mortar: The Right Type for the Job
May 2025

When it comes to masonry construction, mortar is much more than “glue” that holds everything together — it’s a critical component of wall performance, longevity, and aesthetics. It can “make it or break it”. Whether you’re laying a foundation CMU wall or

MASONRY STRONG Podcast, Episode 20 Recap: Mark Kemp, Superior Masonry
May 2025

On this episode of the MASONRY STRONG Podcast, Mark Kemp joins the set to talk about his esteemed career in masonry, how his passion stayed strong throughout the years, and how retirement has been treating him.